Sweep Frequency Response Analysis (SFRA) is a diagnostic technique used to assess the mechanical and electrical integrity of power transformers, reactors, and other high-voltage equipment. It is primarily used to detect mechanical deformations, winding movements, and core issues that can arise due to short circuits, transportation stresses, aging, or manufacturing defects.
Principle of SFRA
SFRA measures the electrical transfer function of a transformer over a wide range of frequencies. It does this by injecting a low-voltage sinusoidal signal into one terminal of the transformer and measuring the response at another terminal. The resulting frequency response (gain and phase shift) is compared with reference data or baseline measurements to detect deviations that indicate potential internal faults.
Key Aspects of SFRA:
- Frequency Domain Testing
SFRA operates in the frequency domain, unlike traditional time-domain tests such as winding resistance or insulation resistance measurements.
- Transfer Function Analysis
The test evaluates how different parts of the transformer (windings, core, and connections) respond to varying frequencies.
- Comparison with Reference Data
Results are compared with factory test results or previous field measurements to identify deviations that could indicate internal damage.
Test Procedure
- Equipment Setup
SFRA test equipment includes a frequency generator, a response analyzer, and specialized probes for connection to the transformer.
- Transformer Connection
The test is performed on different winding configurations (e.g., high-voltage (HV) winding, low-voltage (LV) winding, and neutral).
Measurements can be done in open-circuit and short-circuit conditions.
- Frequency Sweep
A sinusoidal signal is applied, sweeping from low (typically 10 Hz) to high frequencies (up to 2 MHz).
- Data Collection & Analysis
The output signal is recorded and analyzed to detect abnormalities.
Interpretation of SFRA Results
Low-Frequency Range (10 Hz – 1 kHz):
Affected by core magnetization, core movement, or lamination defects.
Mid-Frequency Range (1 kHz – 100 kHz):
Indicates winding movement, bulk winding deformation, or electrical insulation issues.
High-Frequency Range (100 kHz – 2 MHz):
Sensitive to minor winding displacements, inter-turn faults, or loose connections.
Comparison Methods:
Baseline Comparison: Comparing with factory test results.
Phase-to-Phase Comparison: Comparing identical windings of the same transformer.
Sister Unit Comparison: Comparing with a similar transformer in the same network.
Historical Comparison: Comparing with previous test results over time.
Advantages of SFRA
✔ Highly Sensitive – Detects mechanical and electrical issues that traditional tests may miss.
✔ Non-Invasive – No need to disassemble the transformer.
✔ Early Fault Detection – Prevents catastrophic failures by identifying issues at an early stage.
✔ Repeatable & Reliable – Provides consistent results over time.
Common Issues Detected by SFRA
✅ Core displacement or deformation
✅ Winding movement due to short circuits
✅ Open or shorted windings
✅ Loose clamping of core or windings
✅ Inter-turn faults
✅ Broken or loose connections
Conclusion
Sweep Frequency Response Analysis (SFRA) is a powerful diagnostic tool for transformer condition assessment. It helps in identifying mechanical and electrical faults that could lead to transformer failure. Regular SFRA testing as part of maintenance strategies enhances the reliability and longevity of power transformers.