Buchholz Relay Testing in Transformers

by

in

The Buchholz Relay is a protective device used in oil-filled transformers to detect internal faults like insulation failure, overheating, or arcing. It is a gas-actuated relay installed between the main tank and the conservator of the transformer.

Purpose of Buchholz Relay Testing:

1. Ensure Proper Functioning – Verifies the relay’s response to internal transformer faults.

2. Detect Gas Accumulation – Identifies insulation breakdown or overheating by analyzing gas bubbles.

3. Confirm Alarm & Trip Signals – Ensures the relay correctly activates alarms or trips the transformer during faults.

Types of Buchholz Relay Tests:

1. Visual Inspection:

Check for leakage, mechanical damage, and oil level inside the relay.

Ensure float switches and mercury contacts are intact.

2. Gas Collection Test:

Open the gas sampling valve and collect gas in a test tube.

Analyze the gas composition (e.g., hydrogen, methane, carbon monoxide) to diagnose faults.

Clear gas: Possible minor overheating.

Dark or burnt smell gas: Serious internal fault.

3. Manual Trip Test (Mechanical Actuation):

Simulate gas accumulation by pressing the relay floats manually.

The first stage (alarm) should activate when the upper float moves.

The second stage (trip) should activate when the lower float moves, simulating a major fault.

4. Oil Flow Test (for sudden pressure faults):

Force oil through the relay to check if the relay activates on sudden pressure changes.

The trip mechanism should operate correctly under a simulated fault condition.

Interpreting Test Results:

✅ Normal Operation:

The relay activates at the correct gas levels or oil flow conditions.

Alarm and trip circuits function as expected.

❌ Abnormal Operation:

No response to gas accumulation → Faulty float mechanism or stuck relay.

False tripping → Faulty contacts or relay misalignment.

Gas presence in the test tube → Internal fault in the transformer (further Dissolved Gas Analysis (DGA) needed).


Leave a comment